Description

The Perkins powered WPS200BS with Leroy Somer alternator is designed comply with Australian and European standards and is available for sale Australia wide.

It is supplied complete with 4 Pole ABB circuit breaker and brand smart controllers including DeepSea and ComAp.

Lockable access doors, long range bunded fuel tank and Powder coated galvanised canopy are ready for your daily heavy duties.

The WPS200BS can also be custom made to an open set depending on requirements and other additional specifications.


Code

WPS200BS

Application

Standby and Prime Power

MAIN DATA

Prime power 200 (kVA) 160 (kW)

Standby power 220 (kVA) 176 (kW)

Voltage, Frequency, pf 415V, 50HZ @ 0.8

Sound pressure 7m 76.9 dBA

ENGINE

Perkins 1106A-70TAG4

Cylinders 6

Speed 1500 rpm

ALTERNATOR

Alternator brand Leroy Somer

Alternator model LSA46.3S3

FUEL CONSUMPTION

Bunded Tank Capacity (standard) – 1087 Litres

Fuel Cons. @ 100% 45.8 l/h

Fuel Cons. @ 75% 36 l/h

Fuel Cons. @ 50% 25 l/h

Fuel Cons. @ 25% l/h

CONTROL SYSTEM

Control system Deepsea PLC-7420

Additional information

Weight 2976 kg
Dimensions 123 × 352 × 216 cm