The Perkins powered WPS200BS with Leroy Somer alternator is designed comply with Australian and European standards and is available for sale Australia wide.

It is supplied complete with 4 Pole ABB circuit breaker and brand smart controllers including DeepSea and ComAp.

Lockable access doors, long range bunded fuel tank and Powder coated galvanised canopy are ready for your daily heavy duties.

The  WPS200BS can also be custom made to an open set depending on requirements and other additional specifications.


Code
WPS200BS

Application
Standby and Prime Power

MAIN DATA
Prime power 200 (kVA) 160 (kW)
Standby power 220 (kVA) 176 (kW)
Voltage, Frequency, pf 415V, 50HZ @ 0.8
Sound pressure 7m 76.9 dBA

ENGINE
Perkins 1106A-70TAG4
Cylinders 6
Speed 1500 rpm

ALTERNATOR
Alternator brand Leroy Somer
Alternator model LSA46.3S3

FUEL CONSUMPTION
Bunded Tank Capacity (standard) – 1087 Litres
Fuel Cons. @ 100% 45.8 l/h
Fuel Cons. @ 75% 36 l/h
Fuel Cons. @ 50% 25 l/h
Fuel Cons. @ 25% l/h

CONTROL SYSTEM
Control system Deepsea PLC-7420

Additional information

Weight 2976 kg